−Table of Contents
Long muon run with all PMTs
| Table 1: Data Files Used | |
|---|---|
| PMT | Data File |
| Middle | 1212-1217_attenuation_PMT14(middle)_1100v_1.5cm-dist.dat |
| Top | 1212-1217_attenuation_PMT18(top)_1100v_1.5cm-dist.dat |
| Bottom | 1212-1217_attenuation_PMT3(bottom)_1100v_1.5cm-dist.dat |
Energy Spectra
Timing Spectra
In this and all subsequent plots, the red line represents the time visible in this plot in which the gain of the middle PMT appears to have increased. This red line represents a time midway through Saturday (12/14/13 around 2:30 PM).
Example Pulse
Comparison to atmospheric pressure
| Figure 11: Atmospheric pressure (and extraneous measurements of weather) in Minneapolis during the time of this run. |
|---|
![]() |
This figure is from wunderground (Their data is taken from NOAA.) from this website: http://www.wunderground.com/history/airport/KMSP/2013/12/12/CustomHistory.html?dayend=17&monthend=12&yearend=2013&req_city=NA&req_state=NA&req_statename=NA&MR=1
The jump in area occurred midway through Saturday (12/14/13 around 2:30 PM). The average pressure before the jump was about 102.6 kPa. The average pressure after the jump was about 101.95 kPa.
According to Wikipedia (http://en.wikipedia.org/wiki/Density_of_air), the density of air is
where P is pressure. R is constant, and T is assumed to be constant.
As described previously here, the energy of a muon through a substance is given by the equation
so the energy loss is given by
Therefore, the energy lost through the atmosphere at 102.6 kPa compared to 101.95 kPa is
Assuming the energy the energy of the muons above the atmosphere is E0=6 GeV and the initial energy of the muons at the scintillator is 4 GeV, the initial energy loss through the atmosphere is 2 Gev. Therefore, the energy loss through the atmosphere at 101.95 kPa is 1.95 GeV.
The equation for energy lost through the scintillator is given by
Therefore, the energy deposited in the scintillator at 102.6 kPa is 5.57 MeV and at 101.95 kPa is 5.58 MeV. This difference is negligible, so pressure change is not a likely cause of the jump in area. Further proof is that the energies of the muons in the top and bottom scintillators do not show this jump as well.



















